Stairwell Pressurisation Calculator

Reference: NFPA 92 / ASHRAE
🌬️ FIRE
Free stairwell pressurisation calculator. Estimate the supply airflow and fan duty to keep a fire stair smoke-free from design pressure, door area and leakage per NFPA 92 / ASHRAE.
Inputs
Results
Was this helpful?
💬 Suggest an improvement
Engineering Intelligence

ℹ About This Calculator

Pressurising a fire escape stair keeps smoke out so occupants can escape and firefighters can work. The supply fan must hold a design pressure across closed doors while also delivering enough air through the doors that are open during evacuation. This calculator estimates the required airflow and fan duty from the design pressure, the door area, the number of open doors and building leakage, to NFPA 92 / ASHRAE smoke-control practice.

The design must satisfy two competing cases: enough pressure with all doors closed (without exceeding the maximum door-opening force), and enough airflow velocity through the doors that are open during egress. A relief or modulating arrangement usually reconciles them. Leakage areas, the number of simultaneously open doors and stack effect all matter. Always design to NFPA 92 or the local smoke-control code and coordinate with the fire strategy.

Pressurisation Airflow Method (NFPA 92)

NFPA 92 / ASHRAE

Step 1 - Flow through each open door Q_door = A_door x velocity, with velocity from the design pressure (Q = A x sqrt(2 dP / rho)).
Step 2 - Add leakage flow through closed doors and construction gaps at the design pressure.
Step 3 - Total supply = open-door flow x number of open doors + total leakage.
Step 4 - Check the door-opening force stays within the code limit at the design pressure.
Step 5 - Select the pressurisation fan for the total airflow plus a margin and system resistance.

Worked Example

For a stair with a 2.0 m² door and a 50 Pa design pressure, the open-door velocity is about √(2 × 50 / 1.2) ≈ 9.1 m/s, giving roughly 18 m³/s per open door before leakage. With two doors assumed open plus construction leakage, the fan is selected for the combined airflow and system resistance, while relief keeps the closed-door force within limits.

Smoke Control, Design Notes

Two design cases

The closed-door case sets the pressure and the door-opening force limit; the open-door case sets the airflow to hold a smoke-blocking velocity. A single fixed fan rarely satisfies both, so a barometric relief damper or a modulating/variable-speed fan is used.

Leakage and stack effect

Real buildings leak through door gaps, construction joints and shafts, and tall buildings have stack effect that helps or hinders depending on season. Realistic leakage areas are essential to a credible airflow.

Coordinate the strategy

Pressurisation is one part of the smoke-control and fire strategy. Coordinate it with the fire alarm interface, door hardware, relief paths and any zoned smoke management, and commission it to the code test criteria.

Frequently Asked Questions

How does stairwell pressurisation work? +
A fan supplies air to the stair so its pressure is higher than the adjacent floors, so smoke cannot enter through leakage or open doors. It keeps the escape route tenable during a fire.
What two conditions must the design meet? +
Enough pressure with all doors closed (without making the doors too hard to open) and enough air velocity through the doors that are open during evacuation. These pull in opposite directions and are reconciled with relief or modulation.
What limits the door-opening force? +
Codes cap the force needed to open a stair door (people must be able to open it), which in turn limits the maximum pressure across a closed door. Excess pressure must be relieved.
How many doors are assumed open? +
Smoke-control design assumes a number of doors open during evacuation (often related to the number of floors), and the fan must maintain the target velocity through them.
Which code governs stair pressurisation? +
NFPA 92 (smoke control systems) and ASHRAE guidance, along with the local building and fire code and the project fire strategy.