ℹ About This Calculator
The width of exit doors, corridors and stairs must be enough to evacuate everyone on the floor within a safe time. This calculator estimates the occupant load from the floor area and use, then applies the code capacity factor (millimetres of width per person) for level components and for stairs to give the minimum required egress width, so you can check door leaves, corridors and staircases against NFPA 101 / IBC.
Occupant load factors and capacity factors come from the adopted life-safety code and vary by occupancy — assembly, business, mercantile, residential and so on. Stairs need more width per person than level components because travel is slower. The calculated width is a minimum; door hardware, handrails and the need for at least two independent exits often govern the final design. Always work to the specific edition of NFPA 101 or IBC adopted for the project.
Egress Width Method (NFPA 101 / IBC)
NFPA 101 / IBC
Step 1 - Occupant load = floor area / occupant load factor for the use (m² per person). Step 2 - Required width = occupant load x capacity factor (mm per person) - larger for stairs than for level egress. Step 3 - Compare with the minimum door/corridor/stair widths in the code and take the greater. Step 4 - Provide at least two remote exits and check that losing one exit still leaves adequate capacity.
Worked Example
A 900 m² business floor with an occupant load factor of 9.3 m²/person gives about 97 occupants. At a level-egress capacity factor of 5 mm/person the required door/corridor width is 97 × 5 ≈ 485 mm, but the code minimum clear door width (typically ≥ 815–900 mm) governs. For stairs at ~7.6 mm/person the width is 97 × 7.6 ≈ 740 mm, again checked against the code minimum stair width.
Means of Egress — Design Notes
Occupant load drives everything
Egress width is only as good as the occupant load behind it. Use the correct load factor for each use within the building and add fixed-seat or posted occupancies where they apply. Mezzanines and accessory spaces contribute to the floor they discharge onto.
Two-exit rule and remoteness
Most occupancies need at least two exits placed remotely so a single fire cannot block both. Capacity is then split between them, and the design is checked with the most demanding exit assumed unavailable.
Beyond width
Clear width is reduced by door hardware, handrails and encroachments, and travel distance, dead-end corridors and discharge arrangements must also comply. Use this tool for the width screen, then complete the full life-safety analysis to code.
Frequently Asked Questions
Related Calculators
Related Articles
🧮 114 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →