ℹ About This Calculator
The sensible heat ratio (SHR) is the share of the cooling load that is sensible (temperature) rather than latent (moisture). It sets the slope of the room process line on the psychrometric chart and therefore the supply air condition needed to hold both temperature and humidity. This calculator finds the room SHR from the sensible and latent loads and helps you check the supply air temperature and airflow so the coil dehumidifies correctly.
Comfort applications typically run SHR around 0.7-0.85; spaces with many people, ventilation air or moisture sources have lower SHR and need deeper coils or colder supply air to remove humidity. If the airflow is set only by the sensible load, a low SHR space can end up warm and humid. Match the coil apparatus dew point and supply condition to the room SHR line, and confirm with a psychrometric analysis.
Sensible Heat Ratio Method
ASHRAE Fundamentals
Step 1 - Total cooling load = sensible load + latent load (kW). Step 2 - SHR = sensible load / total load. Step 3 - A lower SHR means more latent (moisture) load, needing colder/drier supply air. Step 4 - Required supply airflow = sensible load / (1.2 x 1.006 x (room temp - supply temp)). Step 5 - Pick a supply temperature that meets both the sensible airflow and the latent (dehumidification) demand.
Worked Example
A room has a 12 kW sensible and 3 kW latent load. Total = 15 kW, so SHR = 12 / 15 = 0.80. Airflow to carry the sensible load with a 24 °C room and 13 °C supply is 12 / (1.2 × 1.006 × 11) ≈ 0.90 m³/s, and the 13 °C supply must also be dry enough to remove the 3 kW latent load.
Using SHR in Coil Selection
The room line
Plotting the room condition and the SHR slope on the psychrometric chart shows the supply condition the coil must deliver. The steeper the latent demand, the further the supply point drops in both temperature and moisture.
Sensible airflow vs latent demand
Airflow is usually set by the sensible load and the room-to-supply temperature difference, but the chosen supply must also sit low enough on the chart to remove the latent load. In low-SHR spaces this pushes the coil to a lower apparatus dew point.
Watch ventilation and people
Outdoor air and occupancy add most of the latent load. Where these are high, expect a low SHR and design the coil and supply air accordingly, or add dedicated dehumidification.
Frequently Asked Questions
Related Calculators
Related Articles
🧮 114 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →