ℹ About This Calculator
A gas pressure regulator must pass the required flow while dropping the supply pressure to the delivery pressure without starving downstream appliances. This calculator estimates the required valve flow coefficient (Cv) from the inlet pressure, the delivery pressure, the gas flow rate and the gas type, handling both sub-critical and critical (choked) flow, so you can select a regulator with adequate capacity for LPG or natural gas service.
Regulator sizing depends on absolute pressures, so add atmospheric pressure to the gauge values. Gas specific gravity differs (natural gas ~0.6, LPG ~1.5), which changes capacity. Choked flow occurs at high pressure drops and caps the flow regardless of further downstream reduction. Always size for the peak simultaneous demand, allow turndown for low fire, and confirm against the manufacturer capacity tables and the applicable gas code (for example NFPA 54/58).
Regulator Cv Method (Critical / Sub-critical Flow)
NFPA 58 / IGC
Step 1 - Check the pressure ratio: if outlet < about half of absolute inlet, flow is critical (choked). Step 2 - Critical flow: Cv = Q x sqrt(sg) / (constant x P1_abs). Step 3 - Sub-critical flow: Cv = Q x sqrt(sg / (dP x P2_abs)) / constant. Step 4 - Select a regulator whose rated Cv (and turndown) exceeds the required value at the design flow.
Worked Example
Delivering 50 Nm³/hr of natural gas (sg ≈ 0.6) from 1.0 bar g to 21 mbar, the large pressure ratio makes the flow choked, so the required Cv is governed by the absolute inlet pressure. The computed Cv sets the minimum regulator size; a model with rated Cv above this and good turndown is selected.
Regulator Selection Notes
Two-stage regulation
Many installations use two-stage regulation, a first-stage regulator near the source drops high supply pressure to an intermediate value, and a second-stage regulator at the appliance sets the burner pressure. Each stage is sized for its own inlet, outlet and flow.
Choked flow and lock-up
At high pressure drops flow is choked, so extra inlet pressure does not increase capacity. Also check lock-up (the small rise above set pressure at no flow) so appliances are not over-pressured at night or low demand.
Confirm with the maker
Use the calculated Cv to shortlist, then confirm against the manufacturer capacity curves at your exact inlet, outlet and gas, and verify relief and over-pressure protection to the gas code.
Frequently Asked Questions
Related Calculators
Related Articles
🧮 114 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →