ℹ About This Calculator
A diesel generator needs enough on-site fuel to ride through the required outage without a refill. This calculator estimates the total diesel volume from the genset kVA rating, the average load factor, the specific fuel consumption (litres per hour per kVA) and the number of hours of autonomy you must guarantee, then suggests a day-tank and bulk-tank split so you can specify tank capacity and the fill/transfer arrangement.
Specific fuel consumption depends on the engine and load — a rough figure is 0.2-0.28 L/hr per kVA at full load, and higher per-kVA at part load. Day tanks are kept small and close to the engine for safety and are topped up automatically from the bulk tank; local fire and environmental codes govern indoor tank size, bunding and separation. Always confirm the engine manufacturer fuel curve and the authority-having-jurisdiction storage limits before finalising.
DG Fuel Volume Method
ISO 8528
Step 1 - Running kVA = rated kVA x load factor. Step 2 - Hourly fuel = running kVA x specific consumption (L/hr/kVA). Step 3 - Total fuel = hourly fuel x required run time (hours). Step 4 - Add a reserve (typically 10-20%) for unusable bottom volume and margin. Step 5 - Split into a small day tank (a few hours) feeding the engine and a bulk tank for the balance.
Worked Example
A 500 kVA genset runs at 70% load factor with a specific consumption of 0.24 L/hr/kVA and must give 8 hours of autonomy. Running kVA = 500 × 0.70 = 350 kVA. Hourly fuel = 350 × 0.24 = 84 L/hr. Total = 84 × 8 = 672 L, plus ~15% reserve ≈ 775 L. A 1,000 L bulk tank with a 100–200 L day tank comfortably covers it.
DG Fuel Storage — Design Guidance
Day tank vs bulk tank
Almost all installations use a two-tank arrangement: a small day (or service) tank mounted near the engine and a larger bulk tank for the bulk of the autonomy. A transfer pump keeps the day tank topped up; the day tank is deliberately small so the indoor fire load and spill risk stay low.
How much autonomy?
Backup hours are a project decision — a few hours for a commercial standby set, 24-72 hours for a hospital or data centre, and sometimes days for critical or remote sites. Longer autonomy quickly drives large bulk tanks and refuelling logistics, so confirm the real requirement with the client.
Safety and code
Diesel storage is governed by fire and environmental codes covering tank material, bunding (secondary containment), venting, fill points and separation from the building. Size the tank with this tool, but confirm the installation details against the local authority requirements.
Frequently Asked Questions
Related Calculators
Related Articles
🧮 114 Free MEP Calculators
Browse all HVAC, Electrical, Plumbing, Fire, Gas and Mechanical calculators - IS/IBC/ASHRAE compliant, free PDF export.
Browse All Calculators →⚠️ Disclaimer: For preliminary engineering design only. Verify all results with a licensed engineer before use. Full disclaimer →